Metasys n2 binary output (bo) summary – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 368

Advertising
background image

Object ID

Object Name

Default

Off (0) State

On (1) State

BI 10

Multi-Function Output 7 (Z2-23)

0

Off

On

BI 11

Multi-Function Output 8 (Z2-24)

0

Off

On

BI 12

Multi-Function Output 9 (Z2-25)

0

Off

On

BI 13

Safety Interlock Monitor

0

Safety Clear

Safety Set

BI 14

HAND/AUTO Reference Monitor

0

AUTO or OFF

HAND

BI 15

Multi-Function Input 3 Monitor

0

Off

On

BI 16

Multi-Function Input 4 Monitor

0

Off

On

BI 17

Multi-Function Input 5 Monitor

0

Off

On

BI 18

Multi-Function Input 6 Monitor

0

Off

On

BI 19

Multi-Function Input 7 Monitor

0

Off

On

u

Metasys N2 Binary Output (BO) Summary

Table G.8 Metasys N2 Binary Output Summary (Bypass to Metasys N2)

Object ID

Object Name

Default

Off (0) State

On (1) State

BO 1

Run Forward Command

0

Stop

Forward

BO 2

Run Reverse Command

0

Stop

Reverse

BO 3

External Fault (EFB) Command

0

No Fault

Fault (EFB)

BO 4

Fault Reset Command

0

No Reset

Reset

BO 5

Multi-Function Input 3 (Z2-03)

0

Off

On

BO 6

Multi-Function Input 4 (Z2-04)

0

Off

On

BO 7

Multi-Function Input 5 (Z2-05)

0

Off

On

BO 8

Multi-Function Input 6 (Z2-06)

0

Off

On

BO 9

Multi-Function Input 7 (Z2-07)

0

Off

On

BO10

Panel Lock

Note:

Not supported

0

BO 11

Communication Fault Enable

0

FB14 Not Activated if Cable Loss Occurs FB14 Activated if Cable Loss Occurs

G.6 Metasys N2 Point Database

368