B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 277

Advertising
background image

No.

Name

Unit

Default Settings

Drive Model

2A0040

2A0056

2A0069

2A0081

Bypass Model

D030

D046

D059

D074

o2-04

Drive Model Selection

Hex.

6B

6D

6E

6F

E2-11

Motor Rated Power

kW

(HP)

11

(15)

15

(20)

18.5

(25)

22

(30)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

70.44

63.13

57.87

51.79

C5-17

Motor Inertia

kgm

2

0.053

0.076

0.138

0.165

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

39.7

53

65.8

77.2

E2-02

Motor Rated Slip

Hz

1.7

1.6

1.67

1.7

E2-03

Motor No-Load Current

A

11.2

15.2

15.7

18.5

E2-05

Motor Line-to-Line Resistance

Ω

0.23

0.138

0.101

0.079

E2-06

Motor Leakage Inductance

%

19.5

17.2

15.7

19.5

E2-10

Motor Iron Loss for Torque Compensation

W

245

272

505

538

L2-02

Momentary Power Loss Ride-Thru Time

s

1

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

0.9

1

1

1

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.3

0.6

0.6

0.6

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.265

0.244

0.317

0.355

L8-02

Overheat Alarm Level

°C

125

120

120

125

L8-35

Installation Method Selection

2

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model