Setting 2: Intelligent Stall Prevention

The drive adjusts the deceleration rate so the DC bus voltage is kept at the level set to parameter L3-17. This produces the

shortest possible deceleration time while protecting the motor from stalling. The selected deceleration time is disregarded and

the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time.
This function uses the following parameters for adjusting the deceleration rate:
• DC bus voltage gain (L3-20)
• Deceleration rate calculations gain (L3-21)
• Inertia calculations for motor acceleration time (L3-24)
• Load inertia ratio (L3-25)

Note:

The deceleration time is not constant. Do not use Intelligent Stall Prevention in applications where stopping accuracy is a concern. Use

dynamic braking options instead.

Setting 3: StallP + Resistor
Setting 4: High Flux Brake
Setting 5: High Flux Brake 2

n

L3-06: Stall Prevention Level during Run

Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is

automatically reduced in the constant power range (speed beyond base speed).
The Stall Prevention level can be adjusted using an analog input.

No.

Name

Setting Range

Default

L3-06

Stall Prevention Level During Run

30 to 120%

<1>

120%

<1> The upper limit is determined by parameter L8-38, Carrier Frequency Derating Selection.

n

L3-11: Overvoltage Suppression Function Selection

Enables or disables the overvoltage suppression function.

No.

Name

Setting Range

Default

L3-11

Overvoltage Suppression Function Selection

0, 1

0

Setting 0: Disabled

The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an

overvoltage fault. Use this setting if dynamic braking options are installed.

Setting 1: Enabled

When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative

torque limit and increasing the output frequency.

5.8 L: Protection Functions