B.3 b: Application

Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID

control, the Dwell function, Energy Savings, and a variety of other application-related settings.

u

b1: Operation Mode Selection

No.

(Addr.

Hex)

Name

Description

Values

Page

b1-03

(182)

Stopping Method Selection

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

Default: 1

Range: 0 to 3

83

b1-04

(183)

Reverse Operation Selection 0: Reverse enabled

1: Reverse disabled

Default: 1

Range: 0, 1

84

u

b2: DC Injection Braking and Short Circuit Braking

No.

(Addr.

Hex)

Name

Description

Values

Page

b2-01

(189)

DC Injection Braking Start

Frequency

Sets the frequency at which DC Injection Braking starts when “Ramp to stop”

(b1-03 = 0) is selected.

Default: 0.5 Hz

Min.: 0.0

Max.: 10.0

85

b2-02

(18A)

DC Injection Braking

Current

Sets the DC Injection Braking current as a percentage of the drive rated current.

Default: 50%

Min.: 0

Max.: 100

85

b2-03

(18B)

DC Injection Braking Time

at Start

Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

85

b2-04

(18C)

DC Injection Braking Time

at Stop

Sets DC Injection Braking time at stop.

Default: 0.50 s

Min.: 0.00

Max.: 10.00

85

u

b3: Speed Search

No.

(Addr

Hex.)

Name

Description

Values

Page

b3-01

(191)

Speed Search Selection at

Start

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

88

b3-02

(192)

Speed Search Deactivation

Current

Sets the current level at which the speed is assumed to be detected and Speed

Search is ended. Set as a percentage of the drive rated current.

Default: 120%

Min.: 0

Max.: 200

88

b3-03

(193)

Speed Search Deceleration

Time

Sets output frequency reduction time during Speed Search.

Default: 2.0 s

Min.: 0.1

Max.: 10.0

89

b3-04

(194)

V/f Gain during Speed

Search

Determines how much to lower the V/f ratio during Speed Search.

Output voltage during Speed Search equals the V/f setting multiplied by b3-04.

Default:

<1>

Min.: 10%

Max.: 100%

89

b3-05

(195)

Speed Search Delay Time

When using an external contactor on the output side, b3-05 delays executing

Speed Search after a momentary power loss to allow time for the contactor to

close.

Default: 0.2 s

Min.: 0.0

Max.: 100.0

89

b3-06

(196)

Output Current 1 during

Speed Search

Sets the current injected to the motor at the beginning of Speed Estimation

Speed Search. Set as a coefficient for the motor rated current.

Default:

<1>

Min.: 0.0

Max.: 2.0

89

b3-10

(19A)

Speed Search Detection

Compensation Gain

Sets the gain which is applied to the speed detected by Speed Estimation Speed

Search before the motor is reaccelerated. Increase this setting if ov occurs

when performing Speed Search after a relatively long period of baseblock.

Default: 1.05

Min.: 1.00

Max.: 1.20

89

b3-14

(19E)

Bi-Directional Speed Search

Selection

0: Disabled (uses the direction of the frequency reference)

1: Enabled (drive detects which way the motor is rotating)

Default: 1

Range: 0, 1

89

B.3 b: Application