Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 65

Advertising
background image

Figure 4.7

shows the LCD display with a typical drive-specific parameter displayed and no power to the drive. In this example,

the parameter displayed is stored both in the drive and in the bypass controller, so the present value is shown. The parameter

cannot be changed when there is no power present on the drive. All drive-specific parameter numbers will NOT begin with

the letter “Z”.

BYP-OFF

C1-02=

<Drive Off>

Decel Time 1

Figure 4.8 Drive-Specific Parameter

Figure 4.8

shows the LCD display with a typical drive-specific parameter displayed and no power to the drive. In this example,

the parameter displayed is only stored in the drive so the present value of the parameter is not displayed. This parameter cannot

be changed when there is no power present on the drive. All drive-specific parameter numbers will NOT begin with the letter

“Z”.

BYP-OFF

C1-02= 10.0Hz

(0.0 ~ 60.0)

“10.0Hz”

Hand Fref

Figure 4.9 Bypass-Specific Parameter

Figure 4.9

shows the LCD display with a typical bypass-specific parameter displayed. This value can be changed regardless

if there is power present on the drive or not. All bypass-specific parameter numbers will begin with the letter “Z”.

BYP-RUN BYPASS

U1 - 01=

U1 - 01=

U1 - 01=

Monitor

RLY

DRV/BYP

FWD

RSEQ
RREF

Figure 4.10 Drive-Specific Monitors

Figure 4.10

shows the LCD display with drive-specific monitors displayed and no power to the drive. With no power to the

drive, the bypass controller cannot retrieve the information from the drive and the present values of the monitor is replaced

with dashes. Drive-specific monitor numbers begin with “U1”, “U2”, “U3”, “U4”, or “U5”.

BYP-RUN BYPASS

UB-01= 10.6A
U1-02= 10000111
U1-03= 01001100

Bypass Monitors

RLY

DRV/BYP

FWD

RSEQ
RREF

Figure 4.11 Bypass-Specific Monitors

Figure 4.11

shows the LCD display with bypass-specific monitors displayed. Bypass-specific monitor numbers begin with

“UB”.

4.2 Using the HOA Keypad

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

65

4

Start-Up Programming & Operation