Z3: bypass control communication – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 271

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

Z2-14

(8570)

Digital Input 6 Invert Select

0: Normal. Lack of input signal = OFF

1: Invert. Lack of input signal = ON

Default: 0

Range: 0, 1

163

Z2-15

(8571)

Digital Input 7 Invert Select

0: Normal. Lack of input signal = OFF

1: Invert. Lack of input signal = ON

Default: 0

Range: 0, 1

163

Z2-16

(8572)

Digital Input 8 Invert Select

0: Normal. Lack of input signal = OFF

1: Invert. Lack of input signal = ON

Default: 1

Range: 0, 1

163

Z2-23

(8579)

Digital Output 7 Function

Select

Digital Output 1 Function Select

0: Serial Comm Controlled

1: K1 Drive Input Contactor

2: K2 Drive Output Contactor

3: K3 Bypass Contactor

4: K4 Motor 1 Select

5: K5 Motor 2 Select

6: READY (Drive and Bypass)

7: RUN Active (Drive or Bypass)

8: Drive RUN Active

9: Bypass RUN Active

10: HAND Mode Active

11: OFF Mode Active

12: AUTO Mode Active

13: Drive Mode Selected

14: Bypass Mode Selected

15: Drive or Bypass Fault Active

16: Drive Fault Active

17: Bypass Fault Active

18: Auto Transfer Active

19: Serial RUN Command Active

20: Damper Actuator Output

21: ON Always

22: Loss of Load Detected

99: Not Used

Default: 7

Range: 0 to 22; 99

158

Z2-24

(857A)

Digital Output 8 Function

Select

Default: 10

Range: 0 to 22; 99

158

Z2-25

(857B)

Digital Output 9 Function

Select

Default: 12

Range: 0 to 22; 99

158

Z2-26

(857C)

Digital Output 10 Function

Select

Default: 15

Range: 0 to 22; 99

158

u

Z3: Bypass Control Communication

No.

(Addr.

Hex)

Name

Description

Values

Page

Z3-01

(8500)

Serial Communications

Protocol Select

Selects the bypass serial communications protocol.

0: Modbus

1: N2

2: P1

3: BACnet

Default: 3

Range: 0, 3

164

Z3-02

(8501)

Serial Communications

Node Address Select

Selects the bypass serial communications node address.

Default: 1

Min.: 0

Max.: 127

164

Z3-03

(8502)

Serial Communications

Baud Rate Select

Selects the bypass serial communications speed.

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 76800

8: 115200

Default: 3

Range: 0 to 8

164

Z3-04

(8503)

Serial Communications

Parity Select

Selects the bypass serial communications parity.

0: No Parity

1: Even Parity

2: Odd Parity

Default: 0

Range: 0 to 2

164

B.14 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

271