Z3: bypass control communication – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 271

No.
(Addr.
Hex)
Name
Description
Values
Page
Z2-14
(8570)
Digital Input 6 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-15
(8571)
Digital Input 7 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-16
(8572)
Digital Input 8 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 1
Range: 0, 1
Z2-23
(8579)
Digital Output 7 Function
Select
Digital Output 1 Function Select
0: Serial Comm Controlled
1: K1 Drive Input Contactor
2: K2 Drive Output Contactor
3: K3 Bypass Contactor
4: K4 Motor 1 Select
5: K5 Motor 2 Select
6: READY (Drive and Bypass)
7: RUN Active (Drive or Bypass)
8: Drive RUN Active
9: Bypass RUN Active
10: HAND Mode Active
11: OFF Mode Active
12: AUTO Mode Active
13: Drive Mode Selected
14: Bypass Mode Selected
15: Drive or Bypass Fault Active
16: Drive Fault Active
17: Bypass Fault Active
18: Auto Transfer Active
19: Serial RUN Command Active
20: Damper Actuator Output
21: ON Always
22: Loss of Load Detected
99: Not Used
Default: 7
Range: 0 to 22; 99
Z2-24
(857A)
Digital Output 8 Function
Select
Default: 10
Range: 0 to 22; 99
Z2-25
(857B)
Digital Output 9 Function
Select
Default: 12
Range: 0 to 22; 99
Z2-26
(857C)
Digital Output 10 Function
Select
Default: 15
Range: 0 to 22; 99
u
Z3: Bypass Control Communication
No.
(Addr.
Hex)
Name
Description
Values
Page
Z3-01
(8500)
Serial Communications
Protocol Select
Selects the bypass serial communications protocol.
0: Modbus
1: N2
2: P1
3: BACnet
Default: 3
Range: 0, 3
Z3-02
(8501)
Serial Communications
Node Address Select
Selects the bypass serial communications node address.
Default: 1
Min.: 0
Max.: 127
Z3-03
(8502)
Serial Communications
Baud Rate Select
Selects the bypass serial communications speed.
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 76800
8: 115200
Default: 3
Range: 0 to 8
Z3-04
(8503)
Serial Communications
Parity Select
Selects the bypass serial communications parity.
0: No Parity
1: Even Parity
2: Odd Parity
Default: 0
Range: 0 to 2
B.14 Z: Bypass Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
271
B
Parameter List