5.2 b: Application

u

b1: Operation Mode Selection

n

b1-03: Stopping Method Selection

Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.

No.

Parameter Name

Setting Range

Default

b1-03

Stopping Method Selection

0 to 3

1

Setting 0: Ramp to Stop

When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the

active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection or Short Circuit

Braking depending on the selected control mode.

Setting 1: Coast to Stop

When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to

stop. The stopping time is determined by the inertia and the friction in the driven system.

Drive output is shut off

Run

command

Output

frequency

Motor speed

ON

OFF

Figure 5.1 Coast to Stop

Note:

After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do

not enter Run command until it has come to a complete stop. Use DC Injection at Start (

Refer to b2-03: DC Injection Braking Time at

Start on page 85

) or Speed Search (

Refer to b3: Speed Search on page 85

) to restart the motor before it has completely stopped.

Setting 2: DC Injection Braking to Stop

When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time

(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC current set in parameter b2-02

<1>

into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly faster compared

to Coast to Stop.
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.

Motor coasts

DC Injection Braking

with the current set in

b2-02

Run

command

Output

frequency

ON

OFF

Motor speed

Minimum Baseblock

Time (L2-03)

Figure 5.2 DC Injection Braking to Stop