B2: dc injection braking and short circuit braking, B3: speed search, Refer to b2-03: dc injection braking time at – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 85: Or speed search

Advertising
background image

Setting 0: Reverse Enabled

Possible to operate the motor in both forward and reverse directions.

Setting 1: Reverse Disabled

Drive disregards a Reverse run command or a negative frequency reference.

u

b2: DC Injection Braking and Short Circuit Braking

These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.

n

b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).

No.

Name

Setting Range

Default

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

0.5 Hz

b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01,

DC Injection Braking is enabled for the time set in parameter b2-04.

Output

frequency

Time

b2-04

DC Injection

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 5.6 DC Injection Braking at Stop for V/f

Note:

If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency

falls to the value set to E1-09.

n

b2-02: DC Injection Braking Current

Sets the DC Injection Braking current as a percentage of the drive rated current. The carrier frequency is automatically reduced

to 1 kHz when this parameter is set to more than 50%.

No.

Name

Setting Range

Default

b2-02

DC Injection Braking Current

0 to 100%

50%

The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.

Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher

than the level necessary to hold the motor shaft.

n

b2-03: DC Injection Braking Time at Start

Sets the time of DC Injection Braking at start. Used to stop a coasting motor before restarting it or to apply braking torque at

start. Disabled when set to 0.00 s.

No.

Name

Setting Range

Default

b2-03

DC Injection Braking Time at Start

0.00 to 10.00 s

0.00 s

Note:

Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the

motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.

n

b2-04: DC Injection Braking Time at Stop

Sets the time of DC Injection Braking at stop. Used to completely stop a motor with high inertia load after ramp down. Increase

the value if the motor still coasts by inertia after it should have stopped. Disabled when set to 0.00 s.

No.

Name

Setting Range

Default

b2-04

DC Injection Braking Time at Stop

0.00 to 10.00 s

0.50 s

u

b3: Speed Search

The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces and

start the motor operation directly from the detected speed without first stopping the machine.

5.2 b: Application

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

85

5

Programming