Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 165

Advertising
background image

No.

Name

Setting Range

Default

Z3-04

Serial Communications Parity Select

0 to 2

0

Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity

n

Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after

last communicating, no communications occurs within the time set to Z3-06.

No.

Name

Setting Range

Default

Z3-05

Serial Communications Fault Select

0 to 4

1

Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0

An EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Contactors

An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10

Display AL14 alarm on operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault.
A value of 0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Time Select

0.0 s to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

n

Z3-08, Z3-09: BACnet Device Object Identifier

These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09

is the most significant word.

No.

Name

Setting Range

Default

Z3-08

BACnet Device Object Identifier 0

0 to FFFFH

1

Z3-09

BACnet Device Object Identifier 1

0 to 003FH

0

Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 12D687H.
Set Z3-08 to D687H and set Z3-09 to 12H.

n

Z3-10: Cable Loss Pre-set Speed

When a serial communications fault is detected and Z3-05 = 4, the value here will become the frequency reference.

No.

Name

Setting Range

Default

Z3-10

Cable Loss Pre-set Speed

0.0 to 60.0 Hz

0.0 Hz

5.13 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

165

5

Programming