Binary input objects – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 297

Advertising
background image

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AV13

Output Power

0047H

XXXX.X

(for drives rated

above 11 kVA)

XXX.XX

(for drives rated

11 kVA or

lower)

kW

R

AV14

Torque Reference

0048H

XXXX.X

%

R

AV15

MF Input Status

002BH

R

AV16

Drive Status 2

002CH

R

AV17

MF Output Status

002DH

R

AV18

DC Bus Voltage

0031H

XXXXX

Volts

R

AV19

PI Feedback Level

0038H

XXXX.X

%

R

AV20

PI Input Level

0039H

XXXX.X

%

R

AV21

PI Output Level

003AH

XXXX.X

%

R

AV22

Drive SW Num

004DH

XXXXX

R

AV23

Bypass SW Num

8791H

XXXXX

R

AV24

Comm Error Detail

003DH

R

AV25

KVA Setting

003EH

XXXXX

R

AV26

Control Method

0043H

XXXXX

R

AV27

Accel Time

0200H

XXXX.X

0.0 to 6000.0

Sec

W

AV28

Decel Time

0201H

XXXX.X

0.0 to 6000.0

Sec

W

AV29

<1>

Parameter Number

XXXXX

0 to FFFFH

W

AV30

<1>

Parameter Data

XXXXX

0 to FFFFH

W

AV31

Motor Current

8780H

XXXX.X

Amps

R

AV32

120 V to Kx Coils

8790H

XXXXX

Volts

R

<1>

Refer to Accessing Bypass Parameters and the Enter Command on page 301

for an explanation of how to read and write drive parameters not

listed in the analog or binary objects.

u

Binary Input Objects

Table C.7 Binary Input Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BI1

Input Terminal 1

002BH:bit 0

ON

OFF

R

BI2

Input Terminal 2

002BH:bit 1

ON

OFF

R

BI3

Input Terminal 3

002BH:bit 2

ON

OFF

R

BI4

Input Terminal 4

002BH:bit 3

ON

OFF

R

BI5

Input Terminal 5

002BH:bit 4

ON

OFF

R

BI6

Input Terminal 6

002BH:bit 5

ON

OFF

R

BI7

Input Terminal 7

002BH:bit 6

ON

OFF

R

BI8

Multi-Function Out 1

0020H:bit 5

ON

OFF

R

BI9

Multi-Function Out 2

0020H:bit 6

ON

OFF

R

BI10

BYP DI-1 STAT

8781H: bit 0

ON

OFF

R

BI11

BYP DI-2 STAT

8781H: bit 1

ON

OFF

R

BI12

BYP DI-3 STAT

8781H: bit 2

ON

OFF

R

BI13

BYP DI-4 STAT

8781H: bit 3

ON

OFF

R

BI14

BYP DI-5 STAT

8781H: bit 4

ON

OFF

R

BI15

BYP DI-6 STAT

8781H: bit 5

ON

OFF

R

BI16

BYP DI-7 STAT

8781H: bit 6

ON

OFF

R

BI17

BYP DI-8 STAT

8781H: bit 7

ON

OFF

R

BI18

BYP DO-1 STAT

8782H: bit 0

ON

OFF

R

C.6 BACnet Objects Supported

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

297

C

BACnet Communications