4.4 Powering Up the Drive

u

Powering Up the Drive and Operation Status Display

n

Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check

Description

Power supply voltage

208 Vac Bypass Drive: Three-phase 200 to 240 Vac 50/60 Hz

480 Vac Bypass Drive: Three-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (L1, L2, L3).
Check for proper grounding of drive and motor.

Drive output terminals and

motor terminals

Properly wire drive output terminals T1, T2, and T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load and connected

machinery

Decouple the motor from the load.

n

Status Display

Status

Name

Description

Normal

Operation

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-183

ALM

DRV-OFF

U1-01= 00.00Hz

U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

LSEQ

LREF

RLY

DRV/BYP

The data display area displays the frequency reference.

is lit.

Fault

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

DRV-FAULTED

FB01

Safety Open

RLY

DRV/BYP

External fault (example)

Data displayed varies by the type of fault.

Refer to Fault Displays, Causes, and Possible

Solutions on page 176