Figure 5.45 – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 155

n
Z1-14: Run Delay Frequency Reference
Sets the frequency used while delaying the Run command.
No.
Name
Setting Range
Default
Z1-14
Run Delay Frequency Reference
0.0 to 60.0 Hz
<1>
60.0 Hz
<1>
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-15: Interlock Wait Time
When an input is programmed for Interlock and the time set to this parameter is reached before the Interlock input goes active,
a fault will be declared. The default setting of 0.0 will never time out.
No.
Name
Setting Range
Default
Z1-15
Interlock Wait Time
0.0 to 300.0 s
0.0 s
Run Delay with Preset Speed Examples
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Figure 5.45 Run Delay with Preset Speed Example: Default Setting
5.13 Z: Bypass Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
155
5
Programming