Figure 5.45 – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 155

Advertising
background image

n

Z1-14: Run Delay Frequency Reference

Sets the frequency used while delaying the Run command.

No.

Name

Setting Range

Default

Z1-14

Run Delay Frequency Reference

0.0 to 60.0 Hz

<1>

60.0 Hz

<1>

<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

n

Z1-15: Interlock Wait Time

When an input is programmed for Interlock and the time set to this parameter is reached before the Interlock input goes active,

a fault will be declared. The default setting of 0.0 will never time out.

No.

Name

Setting Range

Default

Z1-15

Interlock Wait Time

0.0 to 300.0 s

0.0 s

Run Delay with Preset Speed Examples

VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

t1

t2

t3

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)

Figure 5.45 Run Delay with Preset Speed Example: Default Setting

5.13 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

155

5

Programming

Advertising