n

Speed Estimation Type Speed Search (b3-24 = 1)

This method can be used for a single induction motor connected to a drive. Do not use this method if the motor is one or more

frame size smaller than the drive, at motor speeds above 200 Hz, or when using a single drive to operate more than one motor.
Speed Estimation is executed in the two steps described below:

Step 1: Back EMF Voltage Estimation

This method is used by Speed Search after baseblock (e.g., a power loss where the drive CPU continued to run and the Run

command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage and outputs the

estimated frequency and increases the voltage using the time constant set in parameter L2-04

<1>

. After that, the motor is

accelerated or decelerated to the frequency reference starting from the detected speed. If there is not enough residual voltage

in the motor windings to perform the calculations described above, the drive will automatically proceed to step 2.
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.

AC power

supply

Output

frequency

Output

current

OFF

ON

Starts at the speed
that was detected

Selected
frequency
reference

Min. Baseblock Time

(L2-03)

Several miliseconds

b3 -05 <1>

Figure 5.9 Speed Search after Baseblock

<1> After AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than

the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored

before starting Speed Search.

Step 2: Current Injection

Current Injection is performed when there is insufficient residual voltage in the motor after extended power losses, when Speed

Search is applied with the Run command (b3-01 = 1), or when an External search command is used.
This feature injects the amount of DC current set to b3-06 to the motor and detects the speed by measuring the current feedback.

The drive then outputs the detected frequency and increases the voltage using the time constant set to parameter L2-04

<1>

while looking at the motor current.
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.
The output frequency is reduced if the current is higher than the level in b3-02. When the current falls below b3-02, the motor

speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.

Run command

Output

frequency

Output

current

OFF

ON

b3-02

Starts at the speed
speed that was detected

Waits twice as long as L2-04

Frequency reference
set to the drive

Decelerates at the Speed

Search decel time set to b3-03

1.0 s

Min. Baseblock Time (L2-03)

<1>

Figure 5.10 Speed Search at Start