Setting 30: Motor 2 Overload Contact

When input is open, declare an oL Fault, issue an EF0 fault to the drive, delay per EF0 Fault Delay Time (Z1-30), and open

Bypass (K3) contactors.

Setting 31: HAND Select

When this is selected, the HAND function command will come from a digital input while the HAND key on the HOA operator

will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these

inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the

HOA function to the OFF state.

Setting 32: AUTO Select

When this is selected, the AUTO function command will come from a digital input while the AUTO key on the HOA operator

will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these

inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the

HOA function to the OFF state

Setting 33: DRIVE/BYPASS Select

When this is selected, the DRIVE/BYPASS select function command will come from a digital input while the DRV/BYP key

on the HOA operator will be ignored.
Input OFF: Drive Mode is selected.
Input ON: Bypass Mode is selected.

Setting 34: Fault Reset
Setting 35: External Fault (EF0)
Setting 36: External Fault (EFB)
Setting 37: Run Reverse (AUTO Mode)

n

Z2-09 to Z2-16: Digital Input 1 to 8 Invert Select

No.

Name

Setting Range

Default

Z2-09

Digital Input 1 Invert Select

0, 1

0

Z2-10

Digital Input 2 Invert Select

0, 1

1

Z2-11

Digital Input 3 Invert Select

0, 1

0

Z2-12

Digital Input 4 Invert Select

0, 1

0

Z2-13

Digital Input 5 Invert Select

0, 1

0

Z2-14

Digital Input 6 Invert Select

0, 1

0

Z2-15

Digital Input 7 Invert Select

0, 1

0

Z2-16

Digital Input 8 Invert Select

0, 1

1

n

Bypass Digital Input Invert Settings

Table 5.30 Bypass Digital Input Invert Settings

Setting

Function

Page

0

Normal

163

Setting

Function

Page

1

Invert

163

Setting 0: Normal

Lack of input signal = OFF

Setting 1: Invert

Lack of input signal = ON

n

Z2-23 to Z2-26: Digital Output 7 to 10 Function Select

No.

Name

Setting Range

Default

Z2-23

Digital Output 7 Function Select

0 to 22; 99

7

Z2-24

Digital Output 8 Function Select

0 to 22; 99

10

Z2-25

Digital Output 9 Function Select

0 to 22; 99

12

Z2-26

Digital Output 10 Function Select

0 to 22; 99

15

5.13 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

163

5

Programming