Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 89

Advertising
background image

No.

Name

Setting Range

Default

b3-02

Speed Search Deactivation Current

0 to 200%

120%

n

b3-03: Speed Search Deceleration Time

Sets the output frequency reduction ramp used by Current Detection Speed Search (b3-24 = 0) and by the Current Injection

Method of Speed Estimation (b3-24 = 1). The time entered into b3-03 will be the time to decelerate from maximum frequency

(E1-04) to minimum frequency (E1-09).

No.

Name

Setting Range

Default

b3-03

Speed Search Deceleration Time

0.1 to 10.0 s

2.0 s

n

b3-04: V/f Gain during Speed Search

During Speed Search, the output voltage calculated from the V/f pattern is multiplied with this value. Changing this value can

help reduce the output current during Speed Search.

No.

Name

Setting Range

Default

b3-04

V/f Gain during Speed Search

10 to 100%

Determined by

o2-04

n

b3-05: Speed Search Delay Time

In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search

can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close

completely.

No.

Name

Setting Range

Default

b3-05

Speed Search Delay Time

0.0 to 100.0 s

0.2 s

n

b3-06: Output Current 1 during Speed Search

Sets the current injected to the motor at the beginning of Speed Estimation Speed Search as a factor of the motor rated current

set in E2-01. If the motor speed is relatively slow when the drive starts to perform Speed Search after a long period of baseblock,

it may be helpful to increase the setting value. The output current during Speed Search is automatically limited by the drive

rated current.

No.

Name

Setting Range

Default

b3-06

Output Current 1 during Speed Search

0.0 to 2.0

Determined by

o2-04

Note:

Use Current Detection Speed Search if Speed Estimation is not working correctly even after adjusting b3-06.

n

b3-10: Speed Search Detection Compensation Gain

Sets the gain for the detected motor speed of the Speed Estimation Speed Search. Increase the setting only if an overvoltage

fault occurs when the drive restarts the motor.

No.

Name

Setting Range

Default

b3-10

Speed Search Detection Compensation Gain

1.00 to 1.20

1.05

n

b3-14: Bi-Directional Speed Search Selection

Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search.

No.

Parameter Name

Setting Range

Default

b3-14

Bi-Directional Speed Search Selection

0, 1

1

Setting 0: Disabled

The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.

Setting 1: Enabled

The drive detects the motor rotation direction to restart the motor.

5.2 b: Application