Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 88

Advertising
background image

<1> The wait time for Speed Search (b3-05) determines the lower limit.

Notes on Using Speed Estimation Speed Search

• Perform Rotational Auto-Tuning for V/f Control (T1-01 = 3) prior to using Speed Estimation in V/f Control and perform

Stationary Auto-Tuning for Line-to-Line Resistance (T1-01 = 2) again if the there is a change in the cable length between

the drive and motor.

• Use Current Detection to search for speeds beyond 200 Hz if the application is running multiple motors from the same drive

or if the motor is considerably smaller than the capacity of the drive.

• Speed Estimation may have trouble finding the actual speed if the motor cable is very long. Use Current Detection in these

instances.

• Use Current Detection instead of Speed Estimation when operating motors smaller than 1.5 kW because Speed Estimation

might not be able to detect the speed or rotation of these smaller motors, in which case Speed Estimation would stop the

motor.

n

Speed Search Activation

Speed Search can be activated using any of the methods 1 through 5 described below. The Speed Search type must be selected

in parameter b3-24 independent of the activation method.
Method 1. Automatically activate Speed Search with every Run command. External Speed Search commands are ignored.
Method 2. Activate Speed Search using the digital input terminals.
Use the input functions for H1-oo in

Table 5.1

.

Table 5.1 Speed Search Activation by Digital Inputs

Setting

Description

b3-24 = 0

b3-24 = 1

61

External Search

Command 1

Closed: Activate Current Detection Speed Search from the

maximum output frequency (E1-04).

Activate Speed Estimation

Speed Search

62

External Search

Command 2

Closed: Activate Current Detection Speed Search from the

frequency reference.

To activate Speed Search by a digital input, the input must be set together with the Run command or the Run command must

be entered after giving the Speed Search command.
Method 3. After automatic fault restart.
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically perform

Speed Search as specified by b3-24 following a fault.
Method 4. After momentary power loss.
This mode requires that the Power Loss Ride-Thru function is enabled during CPU operation (L2-01 = 1 or 2).

Refer to L2-01:

Momentary Power Loss Operation Selection on page 127

.

Method 5. After external baseblock is released.
The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is

above the minimum frequency when the Baseblock command (H1-oo = 8 or 9) is released.

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

0

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor once Speed Search

is complete.

n

b3-02: Speed Search Deactivation Current

Sets the operating current for Speed Search as a percentage of the drive rated current. Normally there is no need to change

this setting. Lower this value if the drive has trouble restarting.

5.2 b: Application

88

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising