B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 285

Advertising
background image

No.

Name

Unit

Default Settings

Drive Model

4A0362

4A0414

4A0515

4A0675

Bypass Model

B302

B361

B414

B515

B590

o2-04

Drive Model Selection

Hex.

A9

AA

AC

AE

E2-11

Motor rated power

kW (HP)

185

(300)

220

(350)

250

(400

-450)

355

(500

-550)

b3-04

V/f Gain during Speed Search

%

60

60

60

60

b3-06

Output Current 1 during Speed Search

0.7

0.7

0.7

0.7

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

30.57

27.13

21.76

23.84

C5-17

Motor Inertia

kgm

2

3.60

4.10

6.50

12.00

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

310

370

500

650

E2-02

Motor Rated Slip

Hz

1.3

1.3

1.25

1

E2-03

Motor No-Load Current

A

81

96

130

130

E2-05

Motor Line-to-Line Resistance

Ω

0.025

0.02

0.014

0.012

E2-06

Motor Leakage Inductance

%

20

20

20

20

E2-10

Motor Iron Loss for Torque Compensation

W

3200

3700

4700

5560

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

2

L2-03

Momentary Power Loss Min. Basebl. Time

s

1.9

2

2.1

2.3

L2-04

Momentary Power Loss Volt. Recov. Time

s

1

1

1

1

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.864

0.91

1.392

1.667

L8-02

Overheat Alarm Level

°C

130

140

140

140

L8-35

Installation Method Selection

0

0

0

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

100

100

100

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

285

B

Parameter List

Advertising