B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 285

Advertising
background image

No.

Name

Unit

Default Settings

–

Drive Model

–

4A0362

4A0414

4A0515

4A0675

Bypass Model

B302

B361

B414

B515

B590

o2-04

Drive Model Selection

Hex.

A9

AA

AC

AE

E2-11

Motor rated power

kW (HP)

185

(300)

220

(350)

250

(400

-450)

355

(500

-550)

b3-04

V/f Gain during Speed Search

%

60

60

60

60

b3-06

Output Current 1 during Speed Search

–

0.7

0.7

0.7

0.7

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

–

–

–

–

–

b3-26

Start Speed Search Select

–

–

–

–

–

b8-03

Energy Saving Control Filter Time Constant

s

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

–

30.57

27.13

21.76

23.84

C5-17

Motor Inertia

kgm

2

3.60

4.10

6.50

12.00

C6-02

Carrier Frequency Selection

–

7

7

7

7

E2-01

Motor Rated Current

A

310

370

500

650

E2-02

Motor Rated Slip

Hz

1.3

1.3

1.25

1

E2-03

Motor No-Load Current

A

81

96

130

130

E2-05

Motor Line-to-Line Resistance

Ω

0.025

0.02

0.014

0.012

E2-06

Motor Leakage Inductance

%

20

20

20

20

E2-10

Motor Iron Loss for Torque Compensation

W

3200

3700

4700

5560

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

2

L2-03

Momentary Power Loss Min. Basebl. Time

s

1.9

2

2.1

2.3

L2-04

Momentary Power Loss Volt. Recov. Time

s

1

1

1

1

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.864

0.91

1.392

1.667

L8-02

Overheat Alarm Level

°C

130

140

140

140

L8-35

Installation Method Selection

–

0

0

0

0

L8-38

Carrier Frequency Reduction Selection

–

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

100

100

100

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

285

B