5.11 S: Special Parameters

u

S1: Dynamic Audible Noise Control Function

The Dynamic Audible Noise Control Function reduces audible noise by suppressing the output voltage.
This function is available when using V/f Control mode and can help to quickly restore output voltage after an impact has

caused a sudden increase in the time constant. Dynamic Audible Noise Control is useful in applications where load impact is

common.

Procedure

1.

Set S1-01 to 1 to enable Dynamic Audible Noise Control.

Note:

1. When S1-01 is set to 1, the tolerance to impact loading is reduced when compared to V/f Control (without Energy

Saving).

2. Disable Dynamic Audible Noise Control for applications without an impact load.

2.

Responsiveness is increased because the addition of a load causes the level of the current to rise.
Increase the value of S1-02. The flux will become stronger and the torque will rise, but load movement will be minimized

by the Dynamic Audible Noise Control function.
Set S1-03 and S1-04 to a small value. Voltage is recovered quicker during impact load conditions. Under certain

conditions voltage stability may become poor.
Lower the value of S1-05. The voltage level will drop and speed up voltage restoration when the load is increased.

3.

Increase the value of S1-03 to increase the effectiveness of Dynamic Audible Noise Control if the output voltage

remains high.

4.

Decrease the value of S1-06 to increase drive response to an impact load.

5.

When the output voltage is unstable, increase the difference between S1-03 and S1-04 and increase S1-05 and S1-06

to slow the load response.

n

S1-01: Dynamic Audible Noise Control Selection

Reduces audible noise by decreasing the output voltage in variable torque applications with light loads.

No.

Name

Setting Range

Default

S1-01

Dynamic Audible Noise Control Selection

0 or 1

0

Setting 0: Disabled
Setting 1: Enabled

n

S1-02: Voltage Reduction Rate

Sets the rate at which the output voltage will be reduced as a percentage of the V/f pattern when operating with no load.

No.

Name

Setting Range

Default

S1-02

Voltage Reduction Rate

50.0 to 100.0%

50.0%

n

S1-03: Voltage Restoration Level

Sets the level when the drive should start restoring the voltage as a percentage of the drive rated torque.
The voltage is reduced when the torque output has decreased to the level set in S1-03.
The method used to reduce the voltage level is selected in accordance with the characteristics of the voltage reduction rate

defined by the S1-03 and S1-04 settings.

Note:

Setting S1-04 to a value less than that of S1-03 + 10.0 will trigger an oPE02 error.

No.

Name

Setting Range

Default

S1-03

Voltage Restoration Level

0.0 to 90.0%

20.0%