Cause

Possible Solution

Hybrid IC failure on the power board

• Cycle power to the drive.
• If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the power board.

HOA Keypad Display

Fault Name

CPF23

Control Board Connection Error
Connection error between the control board and the drive

Cause

Possible Solution

Hardware is damaged

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered

up).

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the serial

communications network

• Remove the cause of the external fault.
• Remove the external fault input from the controller.
• Verify that the controller program is correct.

An external fault (EF0) digital input became

active.

Remove the cause of the external fault.

Faults FB01 to FB09, FB13, or FB14 were

declared by the bypass controller.

Remove the cause of the bypass controller fault.

HOA Keypad Display

Fault Name

Err

EEPROM Write Error

Data cannot be written to the EEPROM

Cause

Possible Solution

Noise has corrupted data while writing to the

EEPROM

• Press “ENTER” on the HOA keypad.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

FAn

Internal Fan Fault
Fan or magnetic contactor failure

Cause

Possible Solution

Internal cooling fan has malfunctioned

• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative

operation time of the fan maintenance timer with U4-04.

• If the cooling fan has exceeded its expected performance life or is damaged in any other way, follow

the replacement instructions in the

Periodic Inspection & Maintenance

chapter.