T1-04: Motor Rated Current

Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10.0 to 300.0% of drive rated

current

Determined by

o2-04

n

T1-05: Motor Base Frequency

Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or

the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 240.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles

Sets the number of motor poles according to the motor nameplate value.

No.

Name

Setting Range

Default

T1-06

Number of Motor Poles

2 to 48

4

n

T1-07: Motor Base Speed

Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor

with an extended speed range or if using the motor in the field weakening area.

No.

Name

Setting Range

Default

T1-07

Motor Base Speed

1750 r/min

n

T1-11: Motor Iron Loss

Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron

loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value

listed to T1-11 if the motor test report is available.

No.

Name

Setting Range

Default

T1-11

Motor Iron Loss

0 to 65535 W

14 W

4.7 Auto-Tuning