Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 98

Advertising
background image

n

b5-16: PID Sleep Delay Time

Sets the delay time to activate or deactivate the PID Sleep function.

No.

Name

Setting Range

Default

b5-16

PID Sleep Delay Time

0.0 to 25.5 s

0.0 s

n

b5-17: PID Accel/Decel Time

The PID acceleration/deceleration time is applied on the PID setpoint value.
When the setpoint changes quickly, the normal C1-oo acceleration times reduce the responsiveness of the system as they

are applied after the PID output. The PID accel/decel time helps avoid the hunting and overshoot and undershoot that can

result from the reduced responsiveness.
The PID acceleration/deceleration time can be canceled using a digital input programmed for “PID SFS cancel” (H1-oo =

34).

No.

Name

Setting Range

Default

b5-17

PID Accel/Decel Time

0.0 to 6000.0 s

0.0 s

n

b5-18: PID Setpoint Selection

Enables or disables parameter b5-19 for PID setpoint.
Refer to

Figure 5.15

for the digital operator home screen display when PID is enabled and b5-18 is set to 1, enabling PID

Setpoint Selection.

U5-99= 30.00%

U5-01= 50.55%

U5-02= -50.55%

PID Setpoint Cmd

- MODE -

DRV RDY

LSEQ

RREF

JOG

b5-19= 030.00%

(0.00~100.00)

“0.00%”

PID Setpoint

- MONITR -

DRV RDY

ENTER

ESC

ENTER

Figure 5.15 PID Setpoint Selection Display

No.

Parameter Name

Setting Range

Default

b5-18

PID Setpoint Selection

0, 1

0

Setting 0: Disabled

Parameter b5-19 is not used as the PID setpoint.

Setting 1: Enabled

Parameter b5-19 is used as PID setpoint.

n

b5-19: PID Setpoint Value

Used as the PID setpoint if parameter b5-18 = 1.

Note:

Values set above b5-38 will be internally limited to b5-38.

No.

Name

Setting Range

Default

b5-19

PID Setpoint Value

0.00 to 100.00%

0.00%

n

b5-20: PID Setpoint Scaling

Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04.

No.

Parameter Name

Setting Range

Default

b5-20

PID Setpoint Scaling

0 to 3

1

Setting 0: 0.01 Hz

The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.

5.2 b: Application

98

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual