Example: When a momentary loss of power occurs, the drive output shuts off and the motor coasts. When power returns, the

drive can find the speed of the coasting motor and restart it directly.
For induction motors, the drive offers two types of Speed Search that can be selected by parameter b3-24 (Speed Estimation

and Current Detection). Both methods are explained below and followed by a description of all relevant parameters.

n

Current Detection Speed Search (b3-24 = 0)

Current Detection Speed Search detects the motor speed by looking at motor current in IM motors. When Speed Search is

started it reduces the output frequency starting from either the maximum output frequency or the frequency reference while

increasing the output voltage using the time set in parameter L2-04

<1>

. As long as the current is higher than the level set to

b3-02, the output frequency is lowered using the time constant set to b3-03. If the current falls below b3-02, the drive assumes

that the output frequency and motor speed are the same and accelerates or decelerates to the frequency reference.
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.
Be aware that sudden acceleration may occur when using this method of Speed Search with relatively light loads.

Figure 5.7

illustrates Current Detection Speed Search operation after a momentary power loss (L2-01 must be set to 1 or 2):

AC power

supply

Output
frequency

Output
current

OFF

ON

Output frequency before
momentary power loss

Selected
frequency
reference

Min. Baseblock Time (L2-03)

Decel time
set to b3-03

Waits for twice
as long as L2-04

Speed Search operation
current set to b3-02

b3-05

Figure 5.7 Current Detection Speed Search after Power Loss

Note:

After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed Search

may start not at the end of L2-03 but even later.

When Speed Search is applied automatically with the Run command, the drive waits for the minimum baseblock time set to

L2-03 before starting Speed Search. If L2-03 is lower than the time set to parameter b3-05, then b3-05 is used as the wait time.

Run command

Output

frequency

Output current

OFF

ON

b3-02

Decel time set
set to b3-03

Waits for twice
as long as L2-04

Selected
frequency
reference

Minimum Baseblock Time

(L2-03)

Max. output frequency
or the specified
frequency reference

Figure 5.8 Current Detection Speed Search at Start or Speed Search Command by Digital Input

Notes on Using Current Detection Type Speed Search

• Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed

Search.

• Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing Speed

Search after power is restored following a momentary power loss.