5.7 H: Terminal Functions

H parameters assign functions to the external terminals.

u

H1: Multi-Function Digital Inputs

n

H1-03 to H1-08: Functions for Terminals S3 to S8

These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in

Table

5.22

.

No.

Parameter Name

Setting

Range

Default

H1-03

Multi-Function Digital Input Terminal S3 Function Selection

3 to 60

24: External Fault

H1-04

Multi-Function Digital Input Terminal S4 Function Selection

3 to 60

14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

3 to 60

3: Multi-Step Speed Reference 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

3 to 60

4: Multi-Step Speed Reference 2

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

3 to 60

6: Jog Reference Selection

H1-08

Multi-Function Digital Input Terminal S8 Function Selection

3 to 60

F: Not Used

Table 5.22 Multi-Function Digital Input Terminal Settings

Setting

Function

Page

3

Multi-Step Speed Reference 1

115

4

Multi-Step Speed Reference 2

6

Jog reference Selection

115

C

Analog Terminal Input Selection

115

F

Not Used

115

10

Up Command

115

11

Down Command

Setting

Function

Page

13

Reverse Jog

116

14

Fault Reset

117

19

PID Disable

117

24

External Fault

117

60

Motor Pre-Heat 1

117

Settings 3 and 4: Multi-Step Speed Reference 1 and 2

Switches multi-step speed frequency references d1-01 to d1-04 by digital inputs.

Refer to d1: Frequency Reference on page

106

for details.

Setting 6: Jog Reference Selection

The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.

Refer to d1:

Frequency Reference on page 106

for details.

Setting C: Analog Terminal Input Selection (Terminals A1, A2, A3)

When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog

terminals.

Setting F: Not Used

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in

the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/

Modbus communications.

Settings 10 and 11: Up/Down Function

The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed

as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input

(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the HOA keypad, the analog inputs, and the pulse

input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in the table below: