Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 226

Advertising
background image

u

Three-Phase 480 Vac Bypass Drive Models B034 to B156

Table A.5 Power Ratings (Three-Phase 480 Vac)

Item

Specification

Bypass Model P1Bo

B034

B040

B052

B065

B077

B096

B124

B156

Maximum Applicable

Motor Capacity (HP)

<1>

25

30

40

50

60

75

100

125

Input

Input Current Range (A)

<2>

39.4

to 40.1

47.3

to 48.0

52.7

to 54.0

65.5

to 66.5

76.7

to 77.6

99.3

to 100.2

128.1

to 129.1

162.2

to 163.1

Rated Voltage

Rated Frequency

Three-phase 480 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency

Fluctuation

±5%

Output

Rated Output Current (A)

34.0

40.0

52.0

65.0

77.0

96.0

124.0

156.0

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

<3>

User-adjustable between 2 and 15 kHz

User-adjustable between

2 and 10 kHz

Maximum Output Voltage (V)

Three-phase 480 Vac

Maximum Output Frequency

(Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.

<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

u

Three-Phase 480 Vac Bypass Drive Models B180 to B590

Table A.6 Power Ratings (Three-Phase 480 Vac)

Item

Specification

Bypass Model P1Bo

B180

B240

B302

B361

B414

B477

B515

B590

Maximum Applicable

Motor Capacity (HP)

<1>

150

200

250

300

350

400

450

500

Input

Input Current Range (A)

<2>

180.6

to 181.5

239.5

to 241.0

290.1

to 291.6

346.5

to 347.9

411.4

to 412.9

433.1

to 435.2

467.4

to 469.5

576.7

to 578.8

Rated Voltage

Rated Frequency

Three-phase 480 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency

Fluctuation

±5%

Output

Rated Output Current (A)

180.0

240.0

302.0

361.0

414.0

477.0

515.0

590.0

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

<3>

User-adjustable between 2 and 10 kHz

User-adjustable between 2 and 5 kHz

Maximum Output Voltage (V)

Three-phase 480 Vac

Maximum Output Frequency

(Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.

<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

226

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising