Bypass control board leds, Alarm (alm) led displays, Auto led and hand led indications – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 62: For details

Advertising
background image

u

Bypass Control Board LEDs

The bypass control board A2 has six bi-color LEDs.
The operational states of the bypass LEDs after completion of the power-up diagnostic LED sequence are described in

Table

4.2

. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying LED states.

Table 4.2 Bypass Control Board LED States

Name

Description

Color

Behavior

MS

Module Status

Red

Not used

Green

Turns ON when transmitting

Turns OFF when receiving

NS

Network Status

Red

Not used

Green

Turns ON when transmitting

Turns OFF when receiving

ST1

ST1, Status 1

Red

Not used

Green

Round status

Toggles ON/OFF every 500 rounds

ST2

ST2, Status 2

Red

Not used

Green

Scan status

Toggles ON/OFF every 500 scans

ST3

ST3, Status 3

Red

Not used

Green

Not used

ST4

ST4, Status 4

Red

Not used

Green

Not used

u

ALARM (ALM) LED Displays

Table 4.3 ALARM (ALM) LED Status and Contents

State

Content

Display

Illuminated

When the drive detects an alarm or error.

Flashing

• When an alarm occurs.
• When an oPE is detected.
• When a fault or error occurs during Auto-Tuning.

Off

Normal operation (no fault or alarm).

u

AUTO LED and HAND LED Indications

Table 4.4 AUTO LED and HAND LED Indications

AUTO LED

HAND LED

State

AUTO

Off

HAND

Off

OFF mode

AUTO

Off

HAND

On solid

HAND mode

AUTO

Off

HAND

Long blink (50% duty)

HAND mode when the Frequency Reference is 0 and/or decelerating in HAND mode.

AUTO

On solid

HAND

Off

Running in AUTO mode

AUTO

Long blink (50% duty)

HAND

Off

Running in AUTO mode when the Frequency Reference is 0 and/or decelerating in AUTO

mode.

4.2 Using the HOA Keypad

62

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual