H5: MEMOBUS/Modbus Serial Communication

n

H5-04: Stopping Method after Communication Error

Selects the stopping method after the drive loses communication with the P1000 Bypass and causes a communications error

(CE).

No.

Name

Setting Range

Default

H5-04

Stopping Method after CE

0 to 3

3

Setting 0: Ramp to Stop

Uses the deceleration time currently enabled.

Setting 1: Coast to Stop
Setting 2: Fast Stop
Setting 3: Alarm Only - Operation Continues