H5: MEMOBUS/Modbus Serial Communication
n
H5-04: Stopping Method after Communication Error
Selects the stopping method after the drive loses communication with the P1000 Bypass and causes a communications error
(CE).
No.
Name
Setting Range
Default
H5-04
Stopping Method after CE
0 to 3
3
Setting 0: Ramp to Stop
Uses the deceleration time currently enabled.
Setting 1: Coast to Stop
Setting 2: Fast Stop
Setting 3: Alarm Only - Operation Continues