Wiring diagram for multiple connections, Network termination, Ms/tp interface – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 291: C.3 connecting to a network

Advertising
background image

u

Wiring Diagram for Multiple Connections

Figure C.3

explains the wiring diagrams for multiple connections using BACnet communication.

n

MS/TP Interface

PLC

IG5

TXRX+

TXRX-

SHLD

+

-

SHLD

Bypass

S1

ON

S1

OFF

IG5

TXRX+

TXRX-

SHLD

Bypass

S1

OFF

IG5

TXRX+

TXRX-

SHLD

Bypass

Bypass
Controller
Board A2

Bypass
Controller
Board A2

Bypass
Controller
Board A2

Figure C.3 Connection Diagram for Multiple Connections

Note:

Turn on DIP switch S1 on the bypass that is located at the end of the network. If S1 is missing, then an external 120 ohm resistor must be

placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is missing,

no external resistor must be used).

u

Network Termination

The two ends of the BACnet network line have to be terminated with a 120 ohm resistor between the TXRX+ and TXRX-

signals. The P1000 Bypass has a built in termination resistor that can be enabled or disabled using DIP switch S1. If a bypass

is located at the end of a network line, enable the termination resistor by setting DIP switch S1 to the ON position. Disable

the termination resistor on all slaves that are not located at the network line end.

Note:

Some bypass controllers do not have DIP switch S1. If this is the case, then an external 120 ohm resistor must be placed across the

TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.

C.3 Connecting to a Network

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

291

C

BACnet Communications

Advertising