L6-13: Motor Underload Protection Selection

Sets Motor Underload Protection (UL6) based on motor load and determines whether the level of L6-02 refers to fbase or

fmax.
Selects the operation of underload detection UL6. Underload is detected when the output current falls below the underload

detection level defined by L6-14 and L2-02

<1>

.

<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.

No.

Name

Setting Range

Default

L6-13

Motor Underload Protection Selection

0, 1

0

Setting 0: Fbase Motor Load Enabled
Setting 1: Fmax Base Motor Load Enabled

UL Detection Level

L6-02

(0 to 300%)

0

Fmin

Fbase

1/f

Fmax

Output
Frequency

L6-14

Motor Underload

Protection at Fmin

Figure 5.39 Motor Underload Protection

n

L6-14: Motor Underload Protection Level at Minimum Frequency

Sets the UL6 detection level at minimum frequency by percentage of drive rated current

No.

Name

Setting Range

Default

L6-14

Motor Underload Protection Level at Minimum Frequency

0 to 300%

15%

u

L8: Drive Protection

n

L8-02: Overheat Alarm Level

Sets the overheat alarm (oH) detection level.
The drive outputs an alarm when the heatsink temperature exceeds the overheat alarm level. If the drive is set to continue

operation after this alarm occurs (L8-03 = 4

<1>

) and the temperature reaches the overheat fault level, the drive will trigger an

oH1 fault and stop operation.
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.
When an output terminal is set for the oH pre-alarm (H2-oo = 20), the switch will close when the heatsink temperature rises

above L8-02.

No.

Name

Setting Range

Default

L8-02

Overheat Alarm Level

50 to 150 °C

Determined by

o2-04

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

5.8 L: Protection Functions