Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 69

Advertising
background image

No.

Name

Description

Values

Page

Z3-03

(8502)

Serial Communications

Baud Rate Select

Baud Rate

Selects the bypass serial communications speed.

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 76800

8: 115200

Default: 3

Range: 0 to 8

164

Z3-04

(8503)

Serial Communications

Parity Select

Parity

Selects the bypass serial communications parity.

0: No Parity

1: Even Parity

2: Odd Parity

Default: 0

Range: 0 to 2

164

Z3-05

(8504)

Serial Communications

Fault Select

Fault Select

Selects the action to take when a serial communications fault is detected.

0: Ignore. A serial communications loss will result in no action being taken.

1: Alarm only.

2: Fault witn EF0. An EF0 will be sent to the drive. If running in Bypass, the

bypass contactor will NOT open and the motor will keep running.

3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive

and the bypass contactor (K3) will be opened.

4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on Operator

Default: 1

Range: 0 to 4

311

Z3-06

(8505)

Serial Communications

Fault Time Select

Fault Time

Sets the time allowed to elapse since receiving serial communications before

triggering a communications fault.

A setting of 0.0 will never time out.

Default: 2.0 s

Min.: 0.0

Max.: 99.9

165

Z3-07

(8506)

Serial Communications

Receive to Transmit Wait

Time

Rx to Tx Wait

Sets the time to delay a serial communications response to a serial

communications command. This parameter will only appear when

Z3-01 = 0, 1, or 2.

Default: 5 ms

Min.: 0

Max.: 99 ms

165

Z3-08

(8507)

BACnet Device Object

Identifier 0

BAC Dev ID0

BACnet only.

Sets the least significant word of 22-bit virtual address. This parameter will

appear only when Z3-01 = 3.

Default: 1

Min.: 0

Max.: FFFF

165

Z3-09

(8508)

BACnet Device Object

Identifier 1

BAC Dev ID1

BACnet only.

Sets the most significant word of 22-bit virtual address. This parameter will

appear only when Z3-01 = 3.

Default: 0

Min.: 0

Max.: 003F

165

Z1-37

(85EA)

Set Time

Set Time

Changes the LCD display to time setting to set the Real Time Clock.

0: Normal display

1: Displays time and date setting modes

Default: 0

Range: 0, 1

161

<1> Values shown are specific to 480 Vac bypass drives.
<2> The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 275

for details.

<3> Default setting is dependent on parameter o2-04, Drive Model Selection.

4.3 The Drive and Programming Modes

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

69

4

Start-Up Programming & Operation

Advertising