L4: speed detection, L5: fault restart – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 251

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

L3-04

(492)

Stall Prevention Selection

during Deceleration

0: Disabled. Deceleration at the active deceleration rate. An ov fault may

occur.

1: General purpose. Deceleration is paused when the DC bus voltage exceeds

the Stall Prevention level.

2: Intelligent. Decelerate as fast as possible while avoiding ov faults.

3: Stall Prevention with braking resistor. Stall Prevention during deceleration

is enabled in coordination with dynamic braking.

4: High Flux Brake

5: High Flux Brake 2

Default: 1

Range: 0 to 5

129

L3-06

(494)

Stall Prevention Level

during Run

Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current. Default: 120%

Min.: 30
Max.: 120

<1>

130

L3-11

(4C7)

Overvoltage Suppression

Function Selection

Enables or disables the ov suppression function, which allows the drive to

change the output frequency as the load changes to prevent an ov fault.

Default: 0

Range: 0, 1

130

L3-25

(46F)

Load Inertia Ratio

Sets the ratio between the motor and machine inertia.

Default: 1.0

Min.: 1.0

Max.: 1000.0

131

<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

Description

Values

Page

L4-05

(49D)

Frequency Reference Loss

Detection Selection

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency reference is lost.

Default: 0

Range: 0, 1

131

L4-06

(4C2)

Frequency Reference at

Reference Loss

Sets the percentage of the frequency reference that the drive should run with

when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

131

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(49E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,

STo, Uv1.

Default: 0

Min.: 0

Max.: 10

132

L5-02

(49F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

132

L5-03

(4A0)

Time to Continue

Making Fault Restarts

Max Restart Time

Enabled only when L5-05 is set to 0. Causes a fault if a fault

restart cannot occur after the set time passes.

Default: 180.0 s

Min.: 0.5

Max.: 180.0

132

L5-04

(46C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 10.0 s

Min.: 0.5

Max.: 600.0

134

L5-05

(467)

Fault Reset Operation

Selection

Fault Reset Sel

0: Continuous

1: Use L5-04 Time

0: Continuously attempt to restart while incrementing restart

counter only at a successful restart (same as F7 and G7).

1: Attempt to restart with the interval time set in L5-04 and

increment the restart counter with each attempt (same as V7).

Default: 0

Range: 0, 1

134

B.9 L: Protection Function

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

251

B

Parameter List