B.15 Defaults by Drive Model

The following tables show parameters and default settings that change with the drive model selection (o2-04).

Table B.4 208 Vac Bypass Drive Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

2A0004

2A0006

2A0008

Bypass Model

D002

D003

D004

D007

o2-04

Drive Model Selection

Hex.

62

63

64

E2-11

Motor Rated Output

kW (HP)

0.75

(0.75)

1.1

(1)

1.5

(2)

b3-04

V/f Gain during Speed Search

%

100

100

100

b3-06

Output Current 1 during Speed Search

1

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

223.7

196.6

169.4

C5-17

Motor Inertia

kgm

2

0.0028

0.0068

0.0068

C6-02

Carrier Frequency Selection

7

7

7

E2-01

Motor Rated Current

A

3.3

4.9

6.2

E2-02

Motor Rated Slip

Hz

2.5

2.6

2.6

E2-03

Motor No-Load Current

A

1.8

2.3

2.8

E2-05

Motor Line-to-Line Resistance

Ω

5.156

3.577

1.997

E2-06

Motor Leakage Inductance

%

13.8

18.5

18.5

E2-10

Motor Iron Loss for Torque Compensation

W

26

38

53

L2-02

Momentary Power Loss Ride-Thru Time

s

0.1

0.2

0.3

L2-03

Momentary Power Loss Minimum Baseblock Time

s

0.3

0.4

0.4

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.3

0.3

0.3

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.142

0.142

0.166

L8-02

Overheat Alarm Level

°C

115

115

115

L8-35

Installation Method Selection

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

275

B

Parameter List

Advertising