U4: maintenance monitors, For a complete list of u4 – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 264

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U3-33

(3017)

Date Year at 5th Most

Recent Fault

Displays the year when the fifth most recent fault occurred.

No signal output

available

U3-34

(3018)

Date Month and Day at 5th

Most Recent Fault

Displays the date and day when the fifth most recent fault occurred.

No signal output

available

U3-35

(3019)

Time Hours and Minutes

at 5th Most Recent Fault Displays the time when the fifth most recent fault occurred.

No signal output

available

U3-36

(301A)

Date Year at 6th Most

Recent Fault

Displays the year when the sixth most recent fault occurred.

No signal output

available

U3-37

(301B)

Date Month and Day a 6th

Most Recent Fault

Displays the date and day when the sixth most recent fault occurred.

No signal output

available

U3-38

(301C)

Time Hours and Minutes

at 6th Most Recent Fault Displays the time when the most sixth recent fault occurred.

No signal output

available

U3-39

(301D)

Date Year at 7th Most

Recent Fault

Displays the year when the most seventh recent fault occurred.

No signal output

available

U3-40

(301E)

Date Month and Day at 7th

Most Recent Fault

Displays the date and day when the seventh most recent fault occurred.

No signal output

available

U3-41

(301F)

Time Hours and Minutes

at 7th Most Recent Fault Displays the time when the seventh most recent fault occurred.

No signal output

available

U3-42

(3020)

Date Year at 8th Most

Recent Fault

Displays the year when the eighth most recent fault occurred.

No signal output

available

U3-43

(3021)

Date Month and Day 8th at

Most Recent Fault

Displays the date and day when the eighth most recent fault occurred.

No signal output

available

U3-44

(3022)

Time Hours and Minutes

at 8th Most Recent Fault Displays the time when the eighth most recent fault occurred.

No signal output

available

U3-45

(3023)

Date Year at 9th Most

Recent Fault

Displays the year when the ninth most recent fault occurred.

No signal output

available

U3-46

(3024)

Date Month and Day at 9th

Most Recent Fault

Displays the date and day when the ninth most recent fault occurred.

No signal output

available

U3-47

(3025)

Time Hours and Minutes

at 9th Most Recent Fault Displays the time when the ninth most recent fault occurred.

No signal output

available

U3-48

(3026)

Date Year at 10th Most

Recent Fault

Displays the year when the tenth most recent fault occurred.

No signal output

available

U3-49

(3027)

Date Month and Day at

10th Most Recent Fault

Displays the date and day when the tenth most recent fault occurred.

No signal output

available

U3-50

(3028)

Time Hours and Minutes

at 10th Most Recent

Displays the time when the tenth most recent fault occurred.

No signal output

available

u

U4: Maintenance Monitors

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U4-01

(4C)

Cumulative Operation

Time

Displays the cumulative operation time of the drive. The value for the

cumulative operation time counter can be reset in parameter o4-01. Use

parameter o4-02 to determine if the operation time should start as soon as

the power is switched on or only while the Run command is present. The

maximum number displayed is 65535.

Note:

This monitor is only updated every 10 operating hours.

No signal output

available

1 h

U4-02

(75)

Number of Run

Commands

Displays the number of times the Run command is entered. Reset the

number of Run commands using parameter o4-13. This value will reset to

0 and start counting again after reaching 65535.

No signal output

available

1 Time

U4-03

(67)

Cooling Fan Operation

Time

Displays the cumulative operation time of the cooling fan. The default value

for the fan operation time is reset in parameter o4-03. The maximum

number displayed is 65535.

Note:

This monitor is only updated every 10 operating hours.

No signal output

available

1 h

U4-04

(7E)

Cooling Fan Maintenance Displays main cooling fan usage time as a percentage of its expected

performance life. Parameter o4-03 can be used to reset this monitor.

No signal output

available

1%

U4-05

(7C)

Capacitor Maintenance

Displays main circuit capacitor usage time as a percentage of their expected

performance life. Parameter o4-05 can be used to reset this monitor.

No signal output

available

1%

B.13 U: Monitors

264

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual