Melsec-q, 6 sequence program used for positioning control – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 248

Advertising
background image

6 - 28

MELSEC-Q

6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL

Starting conditions

To start the control, the following conditions must be satisfied.
The necessary start conditions must be incorporated in the sequence program so
that the control is not started when the conditions are not satisfied.

Device

Signal name

Signal state

Axis 1 Axis 2 Axis 3 Axis 4

PLC READY signal

ON PLC CPU preparation completed

Y0

QD75 READY signal

ON QD75 preparation completed

X0

Synchronization flag

ON

QD75 buffer memory
Accessible

X1

Axis stop signal

OFF Axis stop signal is OFF.

Y4

Y5

Y6

Y7

M code ON signal

OFF M code ON signal is OFF.

X4

X5

X6

X7

Error detection signal

OFF No error is present.

X8

X9

XA

XB

BUSY signal

OFF BUSY signal is OFF.

XC

XD

XE

XF

Interface
signal

Start complete signal

OFF Start complete signal is OFF.

X10

X11

X12

X13

Drive unit READY signal

ON Drive unit preparation completed

Stop signal

OFF Stop signal is OFF.

Upper limit (FLS)

ON Within limit range

External
signal

Lower limit (RLS)

ON Within limit range

: When the synchronous setting of the PLC CPU is made in the nonsynchronous mode, this must be

provided as an interlock.
When it is made in the synchronous mode, no interlock must be provided in the program because the
flag is turned ON when calculation is run on the PLC CPU.

Advertising