Melsec-q, 15 troubleshooting – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 626

Advertising
background image

15 - 22

MELSEC-Q

15 TROUBLESHOOTING

Classification

of errors

Error
code

Error name

Error

Operation status at error occurrence

Positioning

operation

546

Illegal setting of ABS
direction in unit of
degree

The setting value of ABS direction in
the unit of degree is as follows.

• Set outside the setting range.

• A figure other than "0" is set when

the software stroke limit is valid.

At start: The system will not operate.

During operation:

The system decelerates to a
stop.

(Note that, in the continuous
positioning control and continuous
path control, the system continues
operating with the setting set at the
time of start even if the setting is
changed during the operation.)

800

Hold error

In the PLC CPU unit parameter
"Output at error stop", the setting for
QD75 is "Hold".

At start: The system will not operate.
During operation:

The system stops with the
setting (deceleration
stop/sudden stop) of the
detailed parameter 2 sudden
stop selection
(stop group 3).

(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)

801

Flash ROM write
error

Data is not written to the flash ROM.

802

Flash ROM sum
check error

While data is written to the flash
ROM, the power is turned OFF.

At start: The system will not operate.

803

PLC CPU error

The PLC CPU resulted in an error.

804

Dedicated instruction
error

• The ABRST

instruction is

executed with the status set to
other than 0.

• The PSTRT

instruction is

executed with the start No. set to
other than 10 to 600, 7000 to 7004
and 9001 to 9004.

• The TEACH

instruction is

executed with the teaching data
selection set to other than 0 and 1.

• The TEACH

instruction is

executed with the positioning data
No. set to other than 1 to 600.

• The instruction of a non-existent

axis is specified by the ABRST

,

PSTRT

or TEACH

instruction.

At start: The system will not operate.

During operation:

The system stops with the
setting (deceleration
stop/sudden stop) of the
detailed parameter 2 sudden
stop selection
(stop group 3).

(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)

805

Flash ROM write
number error

Data is written to the flash ROM
continuously 25 times or more from
the sequence program.

I/F

806

Dedicated instruction
I/F error

Mismatching occurs between the
PLC CPU and QD75.

At start: The system will not operate.