4 hardware stroke limit function, Danger, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 508: 1] control details

Advertising
background image

12 - 32

MELSEC-Q

12 CONTROL SUB FUNCTIONS

12.4.4 Hardware stroke limit function

!

DANGER

When the hardware stroke limit is required to be wired, ensure to wire it in the negative logic using b-contact.

If it is set in positive logic using a-contact, a serious accident may occur.

In the "hardware stroke limit function", limit switches are set at the upper/lower limit of

the physical moveable range, and the control is stopped (by deceleration stop) by the

input of a signal from the limit switch. Damage to the machine can be prevented by

stopping the control before the upper/lower limit of the physical moveable range is

reached.

Hardware stroke limit switches are normally installed inside the stroke limit/stroke end

on the drive unit side, and the control is stopped before the stroke limit/stoke end on

the drive unit side is reached.

The details shown below explain about the "hardware stroke limit function".

[1] Control details

[2] Wiring the hardware stroke limit

[3] Precautions during control

[4] When the hardware stroke limit is not used

[1] Control details

The following drawing shows the operation of the hardware stroke limit function.

Mechanical stopper

Drive unit

QD75

Movement direction

Deceleration stop at
upper limit switch detection

QD75 control moveable range

Lower limit

Upper limit

Start

Upper limit switch

Lower limit switch

Drive unit
stroke limit

Drive unit
stroke limit

Start

Movement direction

Mechanical stopper

Deceleration stop at
lower limit switch detection

Fig. 12.19 Hardware stroke limit function operation