Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 555

Advertising
background image

12 - 79

MELSEC-Q

12 CONTROL SUB FUNCTIONS

[3] Method of setting target position change function from PLC CPU

The following table and chart show the example of a data setting and sequence

program used to change the target position of the axis 1 by the command from

the PLC CPU, respectively. (example in which the target position value and
command speed are changed to a new target position of "300.0 m" and a new

command speed of "10000.00 mm/min".)

(1) The following data is set.

(Referring to the starting time chart shown in item (2) below, carry out the

setting with the sequence program shown in item (3).)

Buffer memory address

Setting item

Setting

value

Setting details

Axis

1

Axis

2

Axis

3

Axis

4

Cd.27

Target position

value

(new address)

3000

Set the new address.

1534

1535

1634

1635

1734

1735

1834

1835

Cd.28

Target position

value (new speed)

1000000 Set the new speed.

1536

1537

1636

1637

1736

1737

1836

1837

Cd.29

Target position
change request flag

1

Set "1: Carry out speed change".

1538 1638 1738 1838

Refer to Section 5.7 "List of control data" for details on the setting details.

(2) The following shows the time chart for target position change.

PLC READY signal [Y0]

QD75 READY signal [X0]

Start complete signal [X10]

BUSY signal [XC]

Error detection signal [X8]

V

t

Positioning start signal [Y10]

Target position value (new address)

Target position value (new speed)

1000000

3000

Positioning complete signal [X14]

Dwell time

Cd.27

Cd.28

Target position change request flag

1

0

0

Cd.29

Fig. 12.42 Time chart for target position change from PLC CPU