2 details of input signals (qd75 -> plc cpu), Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 63

Advertising
background image

3 - 15

MELSEC-Q

3 SPECIFICATIONS AND FUNCTIONS

3.3.2 Details of input signals (QD75

PLC CPU)

The ON/OFF timing and conditions of the input signals are shown below.

Device

No.

Signal name

Details

X0

QD75 READY

ON:

READY

OFF: Not READY/

Watch dog
timer error

• When the PLC READY signal [Y0] turns from OFF to ON, the parameter setting

range is checked. If no error is found, this signal turns ON.

• When the PLC READY signal [Y0] turns OFF, this signal turns OFF.
• When watch dog timer error occurs, this signal turns OFF.
• This signal is used for interlock in a sequence program, etc.

PLC READY signal [Y0]

OFF

ON

QD75 READY signal [X0] OFF

ON

X1

Synchronization
flag

OFF: Module

access
disabled

ON:

Module
access
enabled

• After the PLC is turned ON or the CPU module is reset, this signal turns ON if the

access from the CPU module to the QD75 is possible.

• When "Asynchronous" is selected in the module synchronization setting of the CPU

module, this signal can be used as interlock for the access from a sequence program
to the QD75.

X4
X5
X6
X7

Axis 1
Axis 2
Axis 3
Axis 4

M code ON

OFF: M code is

not set

ON:

M code is
set

• In the WITH mode, this signal turns ON when the positioning data operation is

started. In the AFTER mode, this signal turns ON when the positioning data
operation is completed.

• This signal turns OFF with the "

Cd.7

M code OFF request".

• When M code is not designated (when "

Da.10

M code" is "0"), this signal will

remain OFF.

• With using continuous path control for the positioning operation, the positioning will

continue even when this signal does not turn OFF. However, a warning will occur.
(Warning code: 503)

• When the PLC READY signal [Y0] turns OFF, the M code ON signal will also turn

OFF.

• If operation is started while the M code is ON, an error will occur.

X8
X9

XA
XB

Axis 1
Axis 2
Axis 3
Axis 4

Error
detection

OFF: No error
ON:

Error
occurrence

• This signal turns ON when an error listed in Section 15.1 occurs, and turns OFF

when the error is reset on "

Cd.5

Axis error rest".

XC
XD
XE

XF

Axis 1
Axis 2
Axis 3
Axis 4

BUSY

1

OFF: Not BUSY
ON:

BUSY

• This signal turns ON at the start of positioning, OPR or JOG operation. It turns OFF

when the "

Da.9

Dwell time" has passed after positioning stops. (This signal

remains ON during positioning.) This signal turns OFF when the positioning is
stopped with step operation.

• During manual pulse generator operation, this signal turns ON while the "

Cd.21

Manual pulse generator enable flag" is ON.

• This signal turns OFF at error completion or positioning stop.

X10
X11
X12
X13

Axis 1
Axis 2
Axis 3
Axis 4

Start
complete

OFF: Start

incomplete

ON:

Start
complete

• This signal turns ON when the positioning start signal turns ON and the QD75 starts

the positioning process.
(The start complete signal also turns ON during OPR control.)

OFF

ON

OFF

ON

Positioning start signal [Y10]

Start complete signal [X10]

X14
X15
X16
X17

Axis 1
Axis 2
Axis 3
Axis 4

Positioning
complete

2

OFF: Positioning

incomplete

ON:

Positioning
complete

• This signal turns ON for the time set in "

Pr.40

Positioning complete signal output

time" from the instant when the positioning control for each positioning data No. is
completed.

(It does not turn ON when "

Pr.40

Positioning complete signal output time" is "0".)

• If positioning (including OPR), JOG/Inching operation, or manual pulse generator

operation is started while this signal is ON, the signal will turn OFF.

• This signal will not turn ON when speed control or positioning is canceled midway.

Advertising