8 - 7

MELSEC-Q

8 OPR CONTROL

Restrictions

A pulse generator with a zero signal is required.
When using a pulse generator without a zero signal, generate a zero signal using an
external signal.

Precautions during operation

(1) An error "Start at OP (error code: 201)" will occur if another machine OPR is

attempted after a machine OPR completion when the OPR retry function is not set

("0" is set in "

Pr.48

OPR retry").

(2) Machine OPR carried out from the near-point dog ON position will start at the

"

Pr.47

Creep speed".

(3) The near-point dog must be ON during deceleration from the OPR speed "

Pr.47

Creep speed".

The workpiece will continue decelerating and stop if the near-point dog is turned OFF

before it has decelerated to the creep speed, thus causing an error "Dog detection
timing fault (error code: 203)".

t

V

ON

OFF

ON

OFF

OFF

0

ON

Near-point dog OFF

In error

Pr. 46 OPR speed

Pr. 47 Creep speed

In OPR

Standing by

Inconsistent

Inconsistent

Value the machine moved is stored

Address at stop

Machine OPR start
(Positioning start signal)

OPR request flag
[ Md.31 Status : b3]

OPR complete flag
[ Md.31 Status : b4]

Md.26 Axis operation status

Md.34 Movement amount
after near-point dog ON

Md.20 Current feed value
Md.21 Machine feed value

Fig. 8.3 Operation when the near-point dog is turned OFF before the creep speed is reached

(4) When a machine OPR is stopped with the stop signal, perform a machine OPR again.

If the restart command is turned ON after a stop with the stop signal, an error "OPR
restart not possible" (error code: 209) occurs.