12 - 29

MELSEC-Q

12 CONTROL SUB FUNCTIONS

[4] Precautions during software stroke limit check

(1) A machine OPR must be executed beforehand for the "software stroke limit

function" to function properly.

(2) During interpolation control, a stroke limit check is carried out for the every

current value of both the reference axis and the interpolation axis. Every
axis will not start if an error occurs, even if it only occurs in one axis.

(3) During circular interpolation control, the "

Pr.12

Software stroke limit upper

limit value"/"

Pr.13

Software stroke limit lower limit value" may be

exceeded.
In this case, a deceleration stop will not be carried out even if the stroke limit
is exceeded. Always install an external limit switch if there is a possibility the
stroke limit will be exceeded.

Arc address ( Da. 7 )

End point address ( Da. 6 )

Axis 1

Axis 1 stroke limit

Deceleration stop not carried out

Starting address

The software stroke limit check is carried out for the following addresses

during circular interpolation control. (Note that " Da. 7 Arc address" is carried

out only for circular interpolation control with sub point designation.

Current value/end point address ( Da. 6 )/arc address ( Da. 7 )

Axis 2

Example

(4) If an error is detected during continuous path control, the axis stops

immediately on completion of execution of the positioning data located right
before the positioning data in error.

Md. 26
Axis operation status

No.10

No.11

No.12

No.13

Immediate stop at
error detection

No.10
P11

No.11
P11

No.12
P11

No.13
P11

No.14
P01

Controlling position

Error occurring

Positioning data

• If the positioning address of positioning data No. 13 is outside the software stroke limit range,

the operation immediately stops after positioning data No. 12 has been executed.

Example