4 led display functions, Qd75p4, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 642: Run err ax1 ax2 ax3 ax4

Advertising
background image

15 - 38

MELSEC-Q

15 TROUBLESHOOTING

15.4 LED display functions

The states of QD75 and each axis control can be confirmed by the LEDs located on

the front panel of the QD75 main unit.

QD75P4

RUN

ERR

AX1
AX2
AX3
AX4

Each axis can be monitored by the states of the LEDs.

The operation and indications of the LEDs are as shown below.

Details of indication

Goes OFF

Goes ON

Flashes

Points to be

confirmed

Error

Remedy

RUN

ERR

AX1
AX2
AX3
AX4

Extinguishment of
RUN LED

The hardware is
faulty or watch dog
timer error occurs.

If the RUN LED does not light up even when the
power is turned ON, the module may be out of order.
Replace the module with a new one.

RUN

ERR

AX1
AX2
AX3
AX4

Lighting of RUN LED,
Extinguishment of
ERR LED

The module is
normal.

RUN

ERR

AX1
AX2
AX3
AX4

Lighting of ERR LED System error

An operation condition setting error or installation PLC
CPU type error occurs.
(The setting and PLC CPU type are outside the
specification range.) Set the PLC CPU type to a one
contained in the specification.

RUN

ERR

AX1
AX2
AX3
AX4

Extinguishment of
AX1 to AX4 LEDs

During axis stop,
during axis standby

RUN

ERR

AX1
AX2
AX3
AX4

Lighting of AX1
(Same even if the
other axis is lit)

During axis
operation

This lights up from the positioning start until the
positioning is completed, stopped temporarily, or
stopped by error (corresponding at a ratio of 1 : 1 to
BUSY signals).

RUN

ERR

AX1
AX2
AX3
AX4

Flashing of ERR LED
Flashing of AX1 LED
(Same even if the
other axis flashes)

Axis error

Check the error observed on the buffer memory batch
processing monitor of a peripheral device and correct
the applicable parameters and positioning data.

RUN

ERR

AX1
AX2
AX3
AX4

Lighting of all LEDs

The hardware is
faulty

The module comes out of order. Replace the module
with a new one.