Melsec-q, 8 opr control – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 291

Advertising
background image

8 - 13

MELSEC-Q

8 OPR CONTROL

(3) If the zero signal is input before the workpiece stops at the stopper, the workpiece

will stop at that position, and that position will be regarded as the OP.

t

ON

OFF

ON

OFF

OFF

ON

V

ON

Zero signal

0

Torque limit

Valid torque limit range

Pr. 47 Creep speed

Pr. 46 OPR speed

Near-point dog OFF

Machine OPR start
(Positioning start signal)

Deviation counter clear output

Md.26 Axis operation status Standing by

Inconsistent

Value the machine moved is stored

OPR request flag
[ Md.31 Status : b3]

OPR complete flag
[ Md.31 Status : b4]

Md.34 Movement amount
after near-point dog ON

Md.20 Current feed value

Md.21 Machine feed value

Standing by

OP address

Inconsistent

In OPR

Stops at stopper

Pr.55 Deviation counter clear signal
output time

Fig. 8.9 Operation when the zero signal is input before the stop at the stopper

(4) Machine OPR started while the near-point dog is ON will start at the "

Pr.47

Creep

speed".

(5) When a machine OPR is stopped with the stop signal, perform a machine OPR again.

If the restart command is turned ON after a stop with the stop signal, an error "OPR
restart not possible" (error code: 209) occurs.

Advertising