9 - 112

MELSEC-Q

9 MAJOR POSITIONING CONTROL

(2) The operation pattern, if set, is ignored in the JUMP instruction.

(3) Positioning control such as loops cannot be executed by conditional JUMP

instructions alone until the conditions have been established.
As the target of the JUMP instruction, specify a positioning data that is
controlled by other than JUMP and NOP instructions.

Positioning data setting example

The following table shows setting examples when "JUMP instruction" is set in
positioning data No. 1 of axis 1.

Setting item

Setting example

Setting details

Da.1 Operation pattern

Setting not required. (Setting value is ignored.)

Da.2 Control system

JUMP

instruction

Set the JUMP instruction.

Da.3 Acceleration time No.

Setting not required. (Setting value is ignored.)

Da.4 Deceleration time No.

Setting not required. (Setting value is ignored.)

Da.5

Axis to be
interpolated

Setting not required. (Setting value is ignored.)

Da.6

Positioning address/
movement amount

Setting not required. (Setting value is ignored.)

Da.7 Arc address

Setting not required. (Setting value is ignored.)

Da.8 Command speed

Setting not required. (Setting value is ignored.)

Da.9 Dwell time

500

Set the positioning data No. 1 to 600 for the JUMP destination. (The
positioning data No. of the JUMP instruction cannot be set. Setting its
own positioning data No. will result in an error "Illegal data No." (error
code: 502).)

A

x

is 1 Positioning data N

o

. 1

Da.10 M code

1

Set the JUMP instruction execution conditions with the condition data
No.

0

:

Unconditional JUMP

1 to 10 :

Condition data No.

("Simultaneous start" condition data cannot be set.)

Refer to Section 5.3 "List of positioning data" for information on the setting details.