12 - 87

MELSEC-Q

12 CONTROL SUB FUNCTIONS

12.7.8 Pre-reading start function

The "pre-reading start function" does not output pulses while the execution prohibition

flag is ON if a positioning start request is given with the execution prohibition flag ON,

and starts outputting pulses within 3m after OFF of the execution prohibition flag is

detected. The positioning start request is given when the axis is in a standby status,

and the execution prohibition flag is turned OFF at the axis operating timing. This

shortens the virtual start time. The QD75 normally takes 6 to 7ms from when it

receives a positioning start request until it starts pulse output (start time). Some

systems often need the start time to be shortened. This "pre-reading start function" can

improve the tact time of the system.

The "pre-reading start function" will be explained below.

[1] Controls

[2] Controlling instructions

[3] Program examples

[1] Controls

The pre-reading start function is performed by turning ON the positioning start

signal [Y10, Y11, Y12, Y13] with the execution prohibition flag [Y14, Y15, Y16,

Y17] ON, or by executing the dedicated instruction (PSTRT1, PSTRT2, PSTRT3,

PSTRT4). However, if positioning is started with the execution prohibition flag

ON, the positioning data is analyzed but pulse output is not provided. While the

execution prohibition flag is ON, "

Md.26

Axis operation status" remains

unchanged from "5: Analyzing". Pulse output starts within 3ms after the execution

prohibition flag [Y14, Y15, Y16, Y17] has turned OFF, and "

Md.26

Axis

operation status" changes to the status (e.g. during position control, during speed

control) that matches the control system. (Refer to Fig. 12.48)

V

Positioning start signal
[Y10,Y11,Y12,Y13]

Execution prohibition flag
[Y14,Y15,Y16,Y17]

BUSY signal
[XC,XD,XE,XF]

OFF

OFF

ON

t

Ta

OFF

ON

ON

Md. 26 Axis operation
status

Start time

Positioning start timing

3ms or less

Positioning data

analysis

Execution prohibition flag OFF waiting

Standby

Analyzing

During position

control

During position

control

Fig. 12.48 Operations of pre-reading start function