12 - 15

MELSEC-Q

12 CONTROL SUB FUNCTIONS

Calculation example

(Conditions)

Movement amount per pulse
No. of pulses per rotation
Unit magnification

: 500 (

µ

m/rev)

: 12000 (pulse/rev)
: 1

(Positioning results)

Command movement amount
Actual movement amount

: 100mm
: 101mm

(Compensation amount)

AL'

5

Ч

10

3

101

Ч

10

3

5050

101

AP'

=

12000

Ч

101

Ч

10

3

=

12000

=

240

Movement amount per pulse
No. of pulses per rotation
Unit magnification

: 101 (

µ

m/rev)

: 240 (pulse/rev)
: 1

[Set in

Pr.3

]

[Set in

Pr.2

]

[Set in

Pr.4

]

(e) Set the post-compensation " Pr.2 No. of pulses per rotation (Ap')",

" Pr.3 Movement amount per rotation (Al')", and " Pr.4 Unit

magnification (Am')" in the parameters, and write them to the QD75.
The set details are validated at the rising edge (OFF ON) of the
PLC READY signal (Y0).

Setting item

Setting

value

Setting details

Pre-compensation

value

Pr.2

No. of pulses per
rotation

A p '

Set the post-compensation value.

Ap

Pr.3

Movement amount
per rotation

A l '

Set the post-compensation value.

Al

Pr.4

Unit magnification

A m '

Set the post-compensation value.

Am

Refer to Section 5.2 "List of parameters" for setting details.