8 - 19

MELSEC-Q

8 OPR CONTROL

Restrictions

When this method is used, a deviation will occur in the stop position (OP)
compared to other OPR methods because an error of about 1 ms occurs in taking
in the near-point dog ON.

Precautions during operation

(1) An error "Count method movement amount fault (error code: 206)" will occur

and the operation will not start if the "

Pr.50

Setting for the movement

amount after near-point dog ON" is smaller than the deceleration distance

from the "

Pr.46

OPR speed" to "

Pr.47

Creep speed".

A deceleration stop will be carried out if the speed is changed during the
operation and an error occurs.

(2) The following shows the operation when a machine OPR is started while the

near-point dog is ON.

Pr.50 Setting for the movement amount after
near-point dog ON

ON

1)

5)

4)

3)

2)

Near-point dog OFF

[Operation when a machine OPR is started at
the near-point dog ON position]

1) A machine OPR is started.
2) The machine moves at the OPR speed in the

opposite direction of an OPR.

3) Deceleration processing is carried out by

"

Pr.39

Stop group 3 sudden stop

selection" when the near-point dog OFF is
detected.

4) After the machine stops, a machine OPR is

carried out in the OPR direction.

5) The machine OPR is completed after moving

the movement amount set in the "

Pr.50

Setting for the movement amount after near-
point dog ON".

Fig. 8.15 Count method 2) machine OPR on the near-point dog ON position

(3) Turn OFF the near-point dog at a sufficient distance from the OP.

Although there is no harm in operation if the near-point dog is turned OFF
during a machine OPR, it is recommended to leave a sufficient distance from
the OP when the near-point dog is turned OFF for the following reason.

If machine OPRs are performed consecutively after the near-point dog is

turned OFF at the time of machine OPR completion, operation will be

performed at the OPR speed until the hardware stroke limit (upper/lower limit)

is reached.

(4) When a machine OPR is stopped with the stop signal, perform a machine

OPR again.
If the restart command is turned ON after a stop with the stop signal, an error
"OPR restart not possible" (error code: 209) occurs.