Melsec-q, 15 troubleshooting – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 618

Advertising
background image

15 - 14

MELSEC-Q

15 TROUBLESHOOTING

Classification

of errors

Error
code

Error name

Error

Operation status at error occurrence

507

Software stroke
limit+

• Positioning is carried out at a

position beyond the software stroke
limit upper limit.

• The positioning address and new

current value exceed the software
stroke limit upper limit.

• In the circular interpolation by the

designation of the sub points, the
sub points exceed the software
stroke limit upper limit.

508

Software stroke
limit–

• Positioning is carried out at a

position beyond the software stroke
limit lower limit.

• The positioning address and new

current value exceed the software
stroke limit lower limit.

• In the circular interpolation by the

designation of the sub points, the
sub points exceed the software
stroke limit lower limit.

At start: The system will not operate.

In the analysis of new current value:

Current value is not
changed.

During operation:

• The system stops

immediately when the
positioning address during
position control (including
position control in speed-
position switching control or
position-speed switching
control) is switched to the
data outside the software
stroke limit range.

• The system makes a stop at

the setting (normal
deceleration stop only) of
sudden stop selection (stop
group 3) in the detailed
parameter 2 when the
current feed value or
machine feed value during
speed control (including
speed control in speed-
position switching control or
position-speed switching
control) or during manual
control falls outside the
software stroke limit range.

514

Outside new current
value range

The new current address is outside
the ranges of 0 to 359.99999, where
the control unit is set to "degree".

515

New current value
not possible

• The control system sets an

operation pattern (continuous path
control) using new current
positioning data.

• The operation pattern sets a "new

current value" in the control system
using the data following the
"continuous path control"
positioning data.

The current value is not changed.

Positioning

operation

516

Continuous path
control not possible

• The continuous path control is

designated using a control system
which is not allowed to use for
continuous path control such as
speed control, speed-position
switching control, position-speed
switching control, and fixed-feed.

• The previous data such as those

on speed control, speed-position
switching control, position-speed
switching control, and fixed-feed
shows a continuous path control.

• The continuous positioning control

is designated for speed control or
position-speed switching control.

At start, the system will not operate.