10 HIGH-LEVEL POSITIONING CONTROL

10.3 Setting the block start data

10.3.1 Relation between various controls and block start data

The " block start data" must be set to carry out "high-level positioning control". The

setting requirements and details of each " block start data" item to be set differ

according to the "

Da.13

Special start instruction" setting.

The following shows the " block start data" setting items corresponding to various

control systems. The operation details of each control type are explained starting in

Section 10.3.2. Also refer to Section 10.4 "Setting the condition data for details on

"condition data" with which control execution is judged.

(The " block start data" settings in this chapter are assumed to be carried out using GX

Configurator-QP.)

High-level positioning

control

Block start data
setting items

Block start

(Normal

start)

Condition

start

Wait start

Simulta-

neous start

Repeated

start

(FOR loop)

Repeated

start

(FOR

condition)

NEXT start

0 : End

Da.11

Shape

1 : Continue

Da.12

Start data No.

1 to 600

Da.13

Special start instruction

0

1

2

3

4

5

6

Da.14

Parameter

Condition data No.

No. of

repetitions

Condition

data No.

: One of the two setting items must be set.

: Set when required (Set to " – " when not used.)

: Setting not possible

: Setting not required (Setting value will be ignored. Use the initial value or a value within the setting range.)

The "NEXT start" instruction is used in combination with "repeated start (FOR loop)" and "repeated start (FOR
condition)". Control using only the "NEXT start" will not be carried out.

REMARK

It is recommended that the "block start data" be set whenever possible with GX

Configurator-QP. Execution by sequence program uses many sequence programs

and devices. The execution becomes complicated, and the scan times will increase.