12 CONTROL SUB FUNCTIONS

[4] Setting the speed change function using an external command

signal

The speed can also be changed using an "external command signal".

The following shows the data settings and sequence program example for

changing the control speed of axis 1 using an "external command signal". (In this

example, the control speed is changed to "10000.00mm/min".)

(1) Set the following data to change the speed using an external command

signal.
(Use the start time chart shown in section (2) below as a reference, and set
using the sequence program shown in section (3).)

Buffer memory address

Setting item

Setting

value

Setting details

Axis

1

Axis

2

Axis

3

Axis

4

Pr.42

External command
function selection

1

Set "1: External speed change request".

62

212

362

512

Cd.8

External command
valid

1

Set "1: Validate the external command".

1505 1605 1705 1805

Cd.14 New speed value

1000000 Set the new speed.

1514

1515

1614

1615

1714

1715

1814

1815

Refer to Section 5.7 "List of control data" for details on the setting details.

(2) The following shows the speed change time chart.

Pr. 42 External command function selection

V

t

0

1

0

1

Md.40 In speed change processing flag

Cd. 14 New speed value

1000000

0

1

0

Cd. 8 External command valid

Dwell time

BUSY signal

Error detection signal

PLC READY signal

Positioning start signal

Positioning complete signal

QD75 READY signal

Start complete signal

[Y10]

[XC]

[X0]

[Y0]

[X10]

[X8]

[X14]

External command signal

Fig. 12.27 Time chart for changing the speed using an external command signal