8 OPR CONTROL

Restrictions

(1) Always limit the servomotor torque after the "

Pr.47

Creep speed" is reached. If the

torque is not limited, the servomotor may fail when the machine presses against the
stopper. (Refer to Section 12.4.2 "Torque limit function".)

(2) Use an external input signal as the zero signal.
(3) The OPR retry function cannot be used in "stopper stop method 3)".

Precautions during operation

(1) If the zero signal is input before the workpiece stops at the stopper, the workpiece

will stop at that position, and that position will become the OP.
At this time an error will not occur.

t

ON

OFF

ON

OFF

OFF

ON

V

0

Pr. 47 Creep speed

Valid torque limit range

Machine OPR start
(Positioning start signal)

Md.26 Axis operation status

Value the machine moved is stored

OPR request flag
[ Md.31 Status : b3]

OPR complete flag
[ Md.31 Status : b4]

Md.34 Movement amount
after near-point dog ON

Md.20 Current feed value

OP address

Inconsistent

Standing by

In OPR

Inconsistent

Standing by

Md.21 Machine feed value

Torque limit

Zero signal

Deviation counter clear output

Stops at stopper

Pr.55 Deviation counter clear signal
output time

Fig. 8.11 When the zero signal is input before the stop at the stopper

(2) When a machine OPR is stopped with the stop signal, perform a machine OPR again.

If the restart command is turned ON after a stop with the stop signal, an error "OPR
restart not possible" (error code: 209) occurs.