12 CONTROL SUB FUNCTIONS

[2] Controlling instructions

(1) The time required to analyze the positioning data is up to 7ms.

(2) After positioning data analysis, the system is put in an execution prohibition

flag OFF waiting status. Any change made to the positioning data in the

execution prohibition flag OFF waiting status is not reflected on the

positioning data. Change the positioning data before turning ON the

positioning start signal.

(3) The pre-reading start function is invalid if the execution prohibition flag is

turned OFF between when the positioning start signal has turned ON and

when positioning data analysis is completed (Ta<start time, Ta: Refer to Fig.

12.48).

(4) The data No. which can be executed positioning start using "

Cd.3

Positioning

start No." with the pre-reading start function are No. 1 to 600 only. Performing

the pre-reading start function at the setting of No. 7000 to 7004 or 9001 to

9004 will result in an outside start No. range error (Error code: 543).

(5) Always turn ON the execution prohibition flag at the same time or before

turning ON the positioning start signal. Pre-reading may not be started if the

execution prohibition flag is turned ON during Ta after the positioning start

signal is turned ON. The pre-reading start function is invalid if the execution

prohibition flag is turned ON after positioning start (pulse output) with the

execution prohibition flag OFF. (It is made valid at the next positioning start.)

[3] Program examples

Pre-reading start function (when positioning start signal Y10 is used)

<Pre-reading start command pulse>

<Sets 1 to positioning start No.>

<Turns ON execution prohibition flag>

<Turns ON positioning start signal>

<Turns OFF execution prohibition flag>

<Turns OFF positioning start signal>